| Sign In | Join Free | My insurersguide.com | 
              
  | 
      
Brand Name : Fanke High-voltage
Model Number : FKFA series
Certification : ISO9001
Place of Origin : Wuhan ,China
MOQ : One Set
Price : Negotiable
Payment Terms : T/T
Supply Ability : 20 sets / month
Delivery Time : 15-20working days
Packaging Details : Export standard wooden case with fumigation free
Usage : CT PT Volt-ampere Characteristics Tester
Test Items : CT/PT volt-ampere ,CT/PT ratio, DC resistance,
Other items : secondary load test functions, angular phase difference, secondary withstand voltage
Test output : 0-2500V adjustable; 0-15A/0-600A/0-1000A
DC resistance : test range : 0.1-20Ω
Secondary load : test output :0-200A
Secondary withstand voltage : test output: 0-2500V
Accuracy : < 0.5%
CT PT Volt-ampere Characteristics Tester , Multifunctional CT PT Testing
I. Product Description:
With the increase requirement of relay protection, the test and check of v-c characteristic carve and the 10% error carve of instrument transformer have became more and more attracting by power system. Based on the absorbing of customers’ suggestion, Fanke has developed a new FKFA voltage-current characteristic comprehensive tester. It adopts high-speed SCM control and inset voltage-up machine, it can test CT voltage-current characteristic, 10% error curve, transformation ratio and polarity on spot. With a special voltage-up transformer, it can do a current-voltage characteristic test for CT/PT within the voltage of 500kV and the current of 1A.
 
II. Test items and technical data
| 
			 Input voltage  | 
			
			 Maximum output voltage  | 
			
			 Maximum output current  | 
			
			 Power  | 
			
			 measurement accuracy  | 
		|||
| 
			 CT volt-ampere output  | 
			220V | 0—2500V | 15A | 3KVA | < 0.5% | ||
| 
			 CT ratio output  | 
			220V | 0-8V | 0—600A/1000AOptional | none | < 0.5% | ||
| 
			 CT ratio measurement  | 
			
			 The maximum ratio display: 999.9K: 5 / 1  | 
			< 0.5% | |||||
| 
			 PT ratio measurement  | 
			
			 The maximum ratio display:999.9K:100,150,100/3,100/  | 
			< 0.5% | |||||
| 
			 DC resistance measurement  | 
			
			 The maximum resistance measurement: 0.1-20Ω  | 
			
			 Less than 1Ω:3% More than 1Ω: <1%  | 
		|||||
| 
			 angular phase difference  | 
			
			 Minimum display: 0.01’ Accuracy::±10’  | 
			
			 Ratio Difference  | 
			
			 Minimum display: 0.01% Accuracy:<0.5%  | 
		||||
| 
			 The secondary load test  | 
			
			 Output Current: 0-200A Time:1~5mins  | 
			The secondary withstand voltage | 
			 output Voltage: 0-2500V Time:1~5mins  | 
		||||
| 
			 Working temperature  | 
			-10~55℃ | 
			 Working voltage  | 
			AC220V(±20%)50HZ | ||||
| 
			 Host volume  | 
			420×300×270 | 
			 Host weight  | 
			26Kg | ||||
| 
                                             | 
                
                        Multifunctional CT PT Testing Equipment Volt Ampere Tester Easy To Operate Images |